Honeywell Searchline Excel 02104-N-XSAU – XNX System, Short range 5–40 m (15–130 ft), UL, 4–20 mA + HART

02104-N-XSAU is a Honeywell Searchline Excel infrared open-path flammable gas detector SKU (XNX System, Short range 5–40 m (15–130 ft), 4–20 mA + HART, UL) for hydrocarbon flammable gas over 0–5 LEL·m. Match the transmitter/receiver pair on the purchase order; do not substitute Searchline Excel Plus/Edge SLXL- codes.

Siblings: output 02104-N-XSAA, approval 02104-N-XSAA, path 02104-N-XLAU.

02104-N-XSAU Honeywell Searchline Excel SR XNX System
Searchline Excel Infrared Open Path Flammable Gas Detector · 02104-N-XSAU

Part-number decode

SegmentMeaningThis SKU
FamilySearchline Excel IR open path02104-
TypeSystem / alignment / accessory / spareXNX System
PathSR 5–40 m / MR 40–120 m / LR 120–200 mShort range 5–40 m (15–130 ft)
Output4–20 mA source or sink, optional Modbus/HART4–20 mA + HART
ApprovalATEX/IECEx, UL, CSA/FM, INMETRO, CU-TRUL
GasHydrocarbon or ethylene curveHydrocarbon
Enclosure316 stainless steel316SS
HandheldAlignment kit includes HHI

Technical specifications

Categorycurrent / XNX System
DescriptionXNX Excel line-of-sight gas detection system, short range (5 to 40m), 4 to 20mA and HART® outputs, UL, fully wired with flexible conduit, electro polished 316SS.
GasHydrocarbon
Path lengthShort range 5–40 m (15–130 ft)
Range0–5 LEL·m
Output4–20 mA + HART
ApprovalsUL
Enclosure316 不锈钢
PrincipleOpen-path IR (xenon flash + solid-state detector)
ResponseT90 < 3 s
IngressIP66/IP67

Why this part number

Order 02104-N-XSAU when the path length, source/sink loop and approval must be locked together: XNX Excel line-of-sight gas detection system, short range (5 to 40m), 4 to 20mA and HART® outputs, UL, fully wired with flexible conduit, electro polished 316SS.. Open-path IR covers vapour clouds that point detectors miss; T90 is under 3 s with xenon-flash solar immunity. If this SKU is short, jump to 02104-N-XSAA (output) or 02104-N-XSAA (approval).

Spares and mates

02104-N-XSAU is Searchline Excel XNX System. The open-path system is 316SS Tx+Rx, 0–5 LEL·m. Matrix: product-9020. Do not substitute Sensepoint XCD cartridges, XNX personalities or Excel Plus/Edge.

Typical applications

02104-N-XSAU is sized for offshore decks, FPSO process areas, tank-farm bunds, compressor halls and pipe racks. Keep the beam clear after alignment; dual-band filters handle fog/rain without software masking.

Selection contrast

P/NTypePathCertOutput
02104-N-XSAAXNX SystemSRATEXsee description
02104-N-XLAUXNX SystemLRUL4–20 mA + HART
02104-N-XLAAXNX SystemLRATEX4–20 mA + HART
02104-N-XLAAUSXNX SystemLRATEX4–20 mA source
02104-N-XLACXNX SystemLRCSA4–20 mA + HART
02104-N-XLSAXNX SystemLRATEX4–20 mA + HART
02104-N-XLSCXNX SystemLRCSA4–20 mA + HART

Searchline Excel family matrix

Installation and service

Align 02104-N-XSAU with the rifle-scope kit until the Tx/Rx optical axis is locked (±0.5°). Path is Short range 5–40 m (15–130 ft); mount on a rigid structure and keep the beam clear. Power is 18–32 VDC. Land 4–20 mA on the fire-and-gas matrix; Modbus uses DVC100(m) MKII or DX100(m). Window heaters are a standard option for severe weather.

FAQ

Is 02104-N-XSAU a point IR head?
No. 02104-N-XSAU is Searchline Excel open-path IR with a separate transmitter and receiver. Point IR is Searchpoint Optima Plus.
Can I rescale 02104-N-XSAU to 0–100 %LEL?
Open-path range is 0–5 LEL·m (alarms typically 1.0 / 3.0 LEL·m). Cross-duct is a different 0–100 %LEL SKU family.
Can I flip source/sink in the field?
No. This SKU is 4–20 mA + HART. Order 02104-N-XSAA for the other loop polarity.
Can I mix SR lamps with LR receivers?
No. 02104-N-XSAU is Short range 5–40 m (15–130 ft). Change span with 02104-N-XLAU; medium/long-range lamps draw more power.
Is 02104-N-XSAU Excel Plus or Edge?
No. Plus/Edge uses SLXL- codes. This family is Searchline Excel IR (02104-N / 2104B).
Can I retap the approval?
No. 02104-N-XSAU is UL. Other approvals are sibling 02104-N-XSAA.

Documents

Searchline Excel IR datasheet · Chinese specification · On-site part-number matrix

Availability and enquiry

Stock is lot-based. If 02104-N-XSAU is out, jump to 02104-N-XSAA / 02104-N-XSAA.