Honeywell XNX XNX-UTAI-MHNNN – no sensor (transmitter body), IR, UL, Aluminium, 3/4" NPT

XNX-UTAI-MHNNN is a Honeywell XNX IR-personality transmitter body, UL / cUL, 4 × 3/4" NPT, LM25 aluminium (painted), Modbus RTU + 4–20 mA HART, local HART port on the transmitter, no sensor. It is the junction-box electronics for Searchpoint Optima Plus or Searchline Excel—not an MPD catalytic transmitter.

Same sensor, swap enclosure/approval: aluminium XNX-UTAI-MHNNN, 316SS XNX-UTSI-MHNNN, other approval XNX-AMAI-MHNNN. XNX-UTAI-MHNNN · XNX-UTSI-MHNNN · XNX-AMAI-MHNNN

XNX-UTAI-MHNNN Honeywell XNX sensor not fitted Aluminium 3/4" NPT

Part-number decode

SegmentMeaningThis SKU
XNXHoneywell XNX universal transmitterXNX
A / UApproval A=ATEX/IECEx; U=UL/cULU
M / TEntry M=M25; T=3/4" NPTT
A / SEnclosure A=aluminium; S=316SSA
V / I / EPersonality V=mV(MPD); I=IR Optima/Excel; E=ECI
N / R / M / FOption N=HART only; R=relays; M=Modbus; F=FFBM
N / HLocal HART port N=no; H=yesH
NNNno sensor (transmitter body)NNN

Same sensor, swap enclosure/approval: aluminium XNX-UTAI-MHNNN, 316SS XNX-UTSI-MHNNN, other approval XNX-AMAI-MHNNN.

Technical specifications

Category变送器本体
PersonalityIR personality (Searchpoint Optima Plus / Searchline Excel)
Sensor / rangeno sensor (transmitter body)
Targetbody / sensor not fitted
Principlepersonality board only
OutputModbus RTU + 4–20 mA HART
Local HARTlocal HART port on the transmitter
Supply16–32 VDC (24 VDC nominal)
EnclosureLM25 aluminium (painted)
Entries4 × 3/4" NPT
DisplayBacklit LCD, magnetic-wand menus
IngressIP66
ApprovalsUL / cUL
Temperature−40~+65 ℃
Massapprox. 2.8 kg
Mates withSearchpoint Optima Plus point IR or Searchline Excel open-path IR

Why this personality / sensor

Optima Plus (point IR) and Excel (open-path) need the IR personality board and a different wiring/power budget than MPD millivolt heads. Ordering an mV body and hoping to hang Excel later will fail at commissioning. This SKU keeps the transmitter certified while the IR head is specified on its own datasheet.

Personality and replaceable parts

XNX-UTAI-MHNNN uses the IR personality (Searchpoint Optima Plus / Searchline Excel) board and mates with Searchpoint Optima Plus point IR or Searchline Excel open-path IR. This SKU ships without a sensor; order the head by gas. Spares live on product-3991. Do not substitute Sensepoint XCD cartridges on XNX.

Typical applications

Use IR bodies on tank-farm open-path runs, compressor-hall Optima points, and LNG boil-off galleries where the path length or window kit is sized after the transmitter is already on the pipe stand.

Selection contrast

P/NGasRangeOptionBody
XNX-UTSI-MHNNNbodyModbus316SS
XNX-AMAI-MHNNNbodyModbusAluminium
XNX-UTAI-NHNNNbodyHARTAluminium
XNX-UTAI-RHNNNbodyRelaysAluminium
XNX-UTAI-FHNNNbodyFFBAluminium

XNX family matrix

Installation and wiring

Wall-mount XNX-UTAI-MHNNN (LM25 aluminium (painted), approx. 2.8 kg) on a rigid stand sized for that mass. This SKU uses 4 × 3/4" NPT entries—glands must match; do not retap XNX-UTAI-MHNNN. Land XNX-UTAI-MHNNN 4–20 mA HART per the loop drawing; relays/Modbus/FFB exist only on the matching option board. Magnetic-wand menus on the XNX-UTAI-MHNNN lid stay non-intrusive. XNX-UTAI-MHNNN is a body: wall-mount the transmitter first and mate the head after the personality is confirmed—do not buy a configured SKU until the gas is frozen.

FAQ

Can I add an MPD sensor to XNX-UTAI-MHNNN later?
XNX-UTAI-MHNNN ships as a transmitter body. mV personalities accept MPD CB1/IV1/IF1/IC1 heads; IR personalities need Optima/Excel; EC personalities need XNX electrochemical cells. Do not mix those three families on this board.
Is XNX-UTAI-MHNNN a complete gas detector?
No. XNX-UTAI-MHNNN is electronics and enclosure only. A configured detector has a three-character sensor code such as CB1 instead of NNN.
When should I swap XNX-UTAI-MHNNN aluminium for 316SS?
Use XNX-UTAI-MHNNN (aluminium, ~2.8 kg) in inland, painted plant. Coastal, splash and sour-water decks should move to stainless sibling XNX-UTSI-MHNNN.
Why is XNX-UTAI-MHNNN NPT instead of M25?
XNX-UTAI-MHNNN is the UL/cUL body and ships 3/4" NPT. Do not tap M25 on this lid—order ATEX sibling XNX-AMAI-MHNNN if metric glands are mandatory.
Can I retrofit Foundation Fieldbus on XNX-UTAI-MHNNN after it ships?
No. XNX-UTAI-MHNNN is the Modbus RTU option board. FFB is a different sales option (XNX-UTAI-FHNNN), not a jumper on this lid.

Documents

Honeywell XNX datasheet / manual · On-site XNX selection matrix

Availability and enquiry

Stock is lot-based. If this box is out, jump to 316SS XNX-UTSI-MHNNN or UL XNX-UTAI-MHNNN rather than a dead SKU.